Key | Issue Type | Summary | Resolution | Note |
---|---|---|---|---|
VIS-4382 | Bug | Webbrowser cover Keypad-Input-Dialogs |
Won't Fix | [[GENERAL]] To open a keypad above a web browser, the "Support client animations and overlay of native elements" feature must be activated in the Visualization Manager. The device must also support this feature. |
VIS-4364 | Bug | Visu: ComboBox Array leads to exception on customer PLC |
Duplicate | |
VIS-4217 | Bug | File Transfer From PLC to Visualization under linux with 'UTF-8 Encoding for STRING' does stop the WebVisu |
Fixed | |
VIS-4194 | Bug | AlarmManager: Exception when a Client is already registered |
Fixed | |
VIS-4186 | Bug | Visualization Extension not compatible with Visu 4.5.0.0 |
Fixed | |
VIS-4177 | Bug | Visu, Combobox: Content not drawn |
Cannot Reproduce | [[GENERAL]] This issue couldn't be reproduced. The investigation indicates that the problem might be related to the provided project. Therefore we cannot provide an immediate fix. |
VIS-4173 | Bug | Visu, IV, Dialogs: Error message ST Code has no assignments when opening Keypad |
Fixed | |
VIS-4153 | Bug | Visualization element Tab Switching via function "Switch frame visualization" does not work |
Fixed | |
VIS-4152 | Bug | Visualization element Tab: When clicking on the last tab, the first tab disappears |
Fixed | |
VIS-4147 | Improvement | Alarms, Re-Alarm: Support Re-Alarm repeat count |
Fixed | |
VIS-4145 | Bug | Save/Load Dialogs do not open if library VisuDialogs is inserted |
Fixed | |
VIS-4142 | Improvement | Alarms, Re-Alarm: Support Re-Alarm notifications from active state |
Fixed | |
VIS-4141 | Bug | Visu: Slow onlinechange due to problem in alarmgroups created before 4.5.0.0 |
Fixed | |
VIS-4110 | Bug | Software Metrics: Trend/Trace is counted as 100 tags |
Won't Fix | [[GENERAL]] The trend/trace represents a functionality that we have defined in this way. In a trend you can see a value progression and not just displaying a variable. So this is not an error. This is as designed. |
VIS-4085 | Bug | Visu, Webserver: Handling of client management errors not correct |
Fixed | |
VIS-4072 | Bug | Alarms: Min. Pending Time not working reliably |
Fixed | |
VIS-4057 | Improvement | Alarms: Replace term confirm by acknlowledge |
Fixed | [[GENERAL]] Additionally to the customer configuration option, there is a new OEMCustomization Hook. If the OEM customization hook is set, the option is automatically set for all new alarm classes. The option "Acknowledge instead of confirm" is than hidden in the alarm class editor. Section: AlarmManagement Key: AckInsteadOfConfirm Datatype: bool |
VIS-4051 | Bug | Refactoring: has no effect in a frame on referenced visualization |
Duplicate | |
VIS-4049 | Improvement | Alarmmanagement: Possiblility to configure how active alarms should behave after restart of the PLC |
Fixed | [[GENERAL]] In the Alarmconfiguration editor in the "Settings" tab the option "Change state of not normal alarms to normal" can be configured. The default in new project is activated. For existing projects, the former behaviour was not changed but it can be adjusted using this option. |
VIS-4043 | Improvement | Add quickfix for "Please do an update of the frame references in the current visualization" |
Duplicate | [[GENERAL]] Duplicates VIS-3927 |
VIS-4029 | Bug | Visu: The project comparison of a project that was processed with different CODESYS versions takes a very long time |
Fixed | |
VIS-4028 | Bug | User Manager Legacy version compiler errors |
Fixed | [[GENERAL]] Additionally to the main bugfix a dedicated compile error is now displayed when the runtime based Visualization Usermanagement is used while the library "CmpUserMgr Implementation" is not available. |
VIS-4021 | Bug | IECVisualization: "VisuFbFrameBase.SetInputPositionData: The element id for the input position cannot be determined" |
Fixed | |
VIS-4008 | Bug | TrendRecording: Error messages in PlcLog get produced when Trend Storage limit is reached |
Fixed | [[GENERAL]] The reason of the logmessages was too less RAM. Using several trends with size limits, this may happen as all of them need RAM when trying to stay at the size limit. In case of not sufficient RAM there will be a switch to the former behaviour of keeping file sizes using “Maximum number of records” which is not this exactly keeping the file size. With the RTS-setting [CmpCAAStorage] MemoryLimitHintInMb the amount of available RAM may be extended. |
VIS-4006 | Bug | Input Configuration, on dialog closed: ST Code is not executed if used VisuDialogs is closed |
Fixed | [[GENERAL]] Affected was only the special case where the element is invisible when receiving the OnDialogClosed event. The element should get this event regardless of visibility state. |
VIS-4000 | Bug | Visu: Input action with counter is executed twice and in scaled visu one action is not done at all |
Fixed | |
VIS-3998 | Improvement | Visu, Trend, DateRange: Improve handling of date range variables in special situations |
Fixed | |
VIS-3997 | Improvement | Visu, Meter: second arrow length should use the style value |
Fixed | |
VIS-3988 | Bug | Visu, Legacy, WV: Backgroundcolor is not visible on change of frame content. |
Fixed | |
VIS-3987 | Bug | Visu, Meter: Paintbug in WV with 2 clients |
Won't Fix | [[GENERAL]] The result of the investigation was that the problem only occurs when switching from Overlay to Legacy. A reload in the browser fixes this problem. |
VIS-3979 | Improvement | Visu, Frame element: Scrollbar shoud be sizeable or style entry for default. |
Fixed | [[GENERAL]] The scrollbar size of the frame and tabcontrol is now configurable. The configuration is per default from style. An individuell value can also be configured. A new style entry can be set: e.g. <Value name="ScrollBar-Size" type="dint">40</Value> The calculation of when a horizontal scrollbar is necessary has not yet taken the ScrollbarSize into account. This has been corrected with this issue. It can now happen that a horizontal scrollbar appears that was not previously displayed. |
VIS-3973 | Bug | Visu, Legacy, Check Box: input configurations bleed through when visu switches to underlying elements |
Fixed | |
VIS-3951 | Bug | HTML5ControlEditor: Not working in 3.5.20.0 environment |
Fixed | |
VIS-3933 | Bug | Visu, Dialogs: Position of dialog can be specified even if not used |
Duplicate | [[GENERAL]] This issue is fixed with VIS-2476. |
VIS-3928 | Bug | Project compare: NullreferenceException with alarm configuration |
Fixed | |
VIS-3927 | Improvement | Visu, Frames: Improved updating of frame references when only parameters have been added |
Fixed | [[GENERAL]] For the compile error "The interface of the referenced visualization ..." it is now possible to update the complete project by a command or by a dialog which opens by doubleclick on the compile error. |
VIS-3926 | Bug | Visu, Frames: MouseLeave events get lost in specific project |
Fixed | |
VIS-3925 | Bug | Visu, Table: Warning from implicit generated code in table element call (string constant too long) |
Fixed | |
VIS-3922 | Bug | Visu Crash with combobox Array on Win CE-Devices |
Fixed | |
VIS-3917 | Bug | Visu, ValueChanged: Frame-Scrollbar accidentally raises OnValueChanged on several elements |
Fixed | |
VIS-3904 | Bug | Visu, Combobox in Groupbox with mouse event crash |
Fixed | [[GENERAL]] The exception could occur in a Combobox if no other element was selected before. This has been fixed and the Combobox will close in this specific case now. |
VIS-3899 | Improvement | Adaption of CODESYS Standard Alarm |
Fixed | [[GENERAL]] In the Alarmconfiguration editor in the "Settings" tab the option "Assign missing inactive timestamps to runtime start" can be configured. The default in new project is activated. For existing projects, the former behaviour was not changed but it can be adjusted using this option. |
VIS-3898 | Improvement | Double Arrows Meter |
Fixed | |
VIS-3883 | Bug | Alarms: CPU Load increase between SP16 and SP19 |
Fixed | |
VIS-3877 | Bug | Visu, AlarmTable: Wrong number of alarms leads to exception with acknowledge all |
Fixed | |
VIS-3869 | Bug | Visu: Old projects with corrupted Guid are broken |
Fixed | |
VIS-3847 | Epic | Visu, Frame: Scrollable frame should display scrollbars only when visible elements are outside the visible range |
Fixed | |
VIS-3846 | Bug | Button Response with delay after pressing Keyboard button |
Fixed | |
VIS-3842 | Improvement | Visu: Blinking shall support color of text |
Fixed | [[GENERAL]] Elements that support blinking and alarm color, also the Table columns and Scrollbar now have a configurable alarm text color under "Text properties -> Font alarm color" for static colors and under "Font variables -> Alarm color" for variables. |
VIS-3834 | Bug | Visu: We get an error when we try to install a library if we don't have exactly the same Visu profile installed as when we created the library |
Won't Fix | [[GENERAL]] Compiled libaries should always be created with the lowest combination of CODESYS Essentials and Add-On versions with which they should be compatible. |
VIS-3831 | Bug | Refactoring,Visu:if a visualisation is renamed the usage in a frame is not udjusted |
Fixed | |
VIS-3824 | Bug | Visu, Trend: element is not updated if several trends are used in the Visu |
Fixed | [[GENERAL]] The originally described issue was not fixed because the missing updates of the trend element were caused by the configuration of that element. The right trend in the customer project uses hardcoded TRUE values for Zoom and Pan and in this state, a trend is not updated automatically by recent values To give customers a hint about the reason for the stopped state of the trend a new symbol is now displayed near the right / top end of the trend axisses. If this symbol appears, then the running trend has been stopped either because zooming or panning is active or the date range is limited to older values by variables. |
VIS-3823 | Improvement | Alarmmanagement: Autoreset for digital alarms after acknowledgement |
Fixed | |
VIS-3817 | Bug | Visu, Trend: No trend update after Online Change |
Duplicate | [[GENERAL]] Duplicates VIS-3791 |
VIS-3815 | Bug | Variable for selected row leads to misalignment error |
Duplicate | |
VIS-3810 | Bug | Compile: Compiler does not check local LibMan placeholder and thus shows error |
Fixed | |
VIS-3801 | Improvement | Visu: Setup version 4.6.0.0 |
Fixed | |
VIS-3791 | Bug | Visu, Trend: Modification of Max Storage size via Online Change stops Trend and does not allow restarting it |
Fixed | |
VIS-3770 | Bug | Visu, Editor: Exception in polygon element with dynamic points |
Fixed | |
VIS-3673 | Epic | Visu, Alarms: It should be possible to add a comment when an alarm is acknowledged |
Fixed | [[COMPATIBILITY_INFORMATION]] Some special unicode characters (e.g. combined surrogates) might not be displayed correctly anymore. This is caused by the following two bugs: CDS-89667, CDS-89833. A reasonable workaround is not possible in the visualization Addon. To switch to the former behavior, the compiler define VISU_ALARMTABLE_COPYWSTRING_COMPATIBLE can be used. |
VIS-3661 | Bug | Visu: Visu libraries not resolved by Visu profile, after adding WebVisu |
Fixed | |
VIS-3647 | Bug | Visu, OnValueChanged: Fix functionality for supported nested elements |
Fixed | |
VIS-3624 | Improvement | Visu: Input configuration, in Frame MouseEvent the ST-Code is not executed |
Fixed | [[GENERAL]] The desired functionality is only implemented for templates with Frame Configuration (Hierarchical Editor). In the Frame Configuration a new standard node "Forward Inputs" can be added. If this node is inserted the frame element referencing this template forwards the inputs events also to the referenced visu even if the frame has already handled the input. Enter and Leave works for one element in the template. Here e.g. hovering can be realized. |
VIS-3596 | Bug | Visu, CamDisplayer: Exception when changing specific value |
Fixed | |
VIS-3556 | Epic | Visu, Alarms: Use lower priority task for storage access |
Fixed | |
VIS-3551 | Bug | Visu, Editor: Fix typo in Frame Selection command |
Fixed | |
VIS-3464 | Improvement | Visu, Frame Configuration: Improve default value handling |
Fixed | [[GENERAL]] The following is implemented: 1. Warning is not generated for EditorType.Text and empty string. Reason. You can see in the element whether the text is configured or not. 2. It is possible to specify a default text for EditorType.Text. This is then entered automatically like the color when creating the element. In addition, the ID from GlobelTextlist is set and the text is added to the GlobalTextList if it does not already exist. |
VIS-3459 | Improvement | Alarm Manager: Implement new acknowledgement method with re-alarm after a specific time not acknowledged |
Duplicate | [[GENERAL]] This issue duplicates VIS-3243 |
VIS-3451 | Bug | Visu Trend: Exception when pressing "Reset" in the display settings |
Fixed | |
VIS-3447 | Improvement | Visu, Trend, Date/Time Picker: Possibility in Trend to set the absolute Min/Max timestamp with two Date/Time Picker |
Duplicate | [[GENERAL]] This issue is a duplicate of VIS-1011 . |
VIS-3445 | Bug | Visu, Table: Warning from implicit generated code in table element call |
Fixed | |
VIS-3428 | Epic | Element List: show licensed Tags for each Element |
Fixed | |
VIS-3423 | Bug | Visu, Scripting: Adding a Visualization via script does not modify the Project Settings as expected |
Fixed | |
VIS-3422 | Bug | Visu, Manager : Unhandled exception when adding new font row |
Fixed | [[GENERAL]] The buttons will not be visible, if no table is shown. |
VIS-3420 | Bug | VisuProperty: Compile Error occurs because property is not set to the application |
Fixed | [[KNOWN_LIMITATIONS]] The bugfix does not affect existing projects! Only the creation of such erroneous projects will now be prevented. In case an existing project has to be fixed, either the compiler defines can be adjusted as proposed by the error messages or the option "Activate property handling in all element properties" can be set again to the desired value by switching on and off if necessary. |
VIS-3417 | Improvement | Alarm Manager: 'Off-delay' for alarms |
Fixed | |
VIS-3405 | Bug | StaticAnalysis, SA0032/33: False positive in Alarm Configuration |
Fixed | |
VIS-3368 | Improvement | Visu: Trend-Interfaces intended for public use should be made visible in the library manager |
Fixed | [[GENERAL]] Some interfaces from library VisuTrendStorageAccess are now public. |
VIS-3323 | Bug | AlarmConfig: Alarms do not work if config is moved to subfolder |
Fixed | |
VIS-3313 | Bug | The edit mode should be left when an element is deactivated |
Fixed | [[GENERAL]] When an element is deactivated the editcontrol or dialog will stay open similiar to when an invalid input is typed. It can still be closed by pressing ESC and the value will not be accepted. In case this feature should cause unexpected problems, it can be disabled by setting the compiler define VISU_NO_INPUTDEACT_CHECK_IN_EDITBOX on the application |
VIS-3257 | Bug | Alarmmanagement: Not all alarm placeholders work |
Fixed | |
VIS-3243 | Improvement | Alarms: Reactivate acknowledged alarm after a certain time if still active |
Fixed | |
VIS-3242 | Bug | FB DateRangeSelector does not work as expected in customer project |
Won't Fix | [[GENERAL]] This issue has already been fixed with VIS-1011. Therefore no change is necessary here. The linked issue provides functionality to read and write the date time ranges of the trend with new control variables. These are accessible in the trend element's properties. |
VIS-3234 | Improvement | Visu, LoginPage: Pages without placeholders should raise warning |
Fixed | [[GENERAL]] There is now a warning if a login visulization has no required placeholders. Required placeholders are USERNAME*, PASSWORD* and LOGIN*. They can be looked up in the Online Help: https://content.helpme-codesys.com/en/CODESYS%20Visualization/_visu_user_management_placeholder.html |
VIS-3230 | Bug | Visu, User Management: CODESYS getting unresponsive with RunTime Based UM and Integrated Visu |
Fixed | |
VIS-3213 | Bug | Visu, Editor: Undo does not work correctly |
Cannot Reproduce | |
VIS-3204 | Improvement | Visu: It should be possible to change target display size defined in device description through VisualizationManager |
Fixed | [[GENERAL]] The existing target settings for the section "TargetDisplaySize” (“width” and “height”) have been extended. The value of the “access” attribute is now evaluated in the targetvisualization editor under Visualization Manager. The input fields for the target visualization setting “Client width”/”Client height” become readonly if the “access” attribute is set to “readonly” or “hide”. In all other cases they will be editable. This option is only active if there is a section “TargetDisplaySize” in the device description. Example: <ts:section name="TargetDisplaySize"> <ts:setting name="width" type="integer" access="readonly"> <ts:value>22</ts:value> </ts:setting> </ts:section> [[COMPATIBILITY_INFORMATION]] There can be a changed behavior in projects in which the target section "TargetDisplaySize” with the settings “width” and “height” has been explicitly added. Because the “access” property hasn’t been evaluated before, it can occur that the input fields “Client width”/”Client height” become editable. The behavior of the targetsettings mentioned before may change, because before this change the access value wasn't evaluated. Now the value is evaluated and could lead to text fields becoming editable. |
VIS-3189 | Bug | font variables: 'Font/Caracter Set' Setting cannot be used |
Fixed | |
VIS-3187 | Bug | Visu, Trend, Exception when open a Trend Element |
Fixed | |
VIS-3184 | Improvement | Visu, Compare: Improve performance of project comparision |
Cannot Reproduce | [[GENERAL]] With the latest visualization version 4.5.0.0 the problem couldn't be seen any more. |
VIS-3153 | Bug | Visu, Combobox Array, Mulitclient: Exception when switching between Touch and non-Touch |
Fixed | |
VIS-2978 | Bug | Visu, WebVisu, Smartphone: Fixed visu sometimes not visible anymore |
Fixed | [[GENERAL]] On smartphones, the browser zooms and scrolls into the webpage if there is an input field open. In some cases this zoom cannot be resetted by the user. Now, the webvisu will reset the zoom in such cases. |
VIS-2934 | Improvement | Visu: Document Visu Selection Constants |
Fixed | [[GENERAL]] The GVL "Visu_Selection_Constants" in library VisuElemBase contains values for ISelectionManager interface. This GVL is now public. |
VIS-2476 | Improvement | Visu, UserManagement: Set position of Login dialog |
Fixed | |
VIS-2069 | Improvement | Combobox, KeyboardHandling: Combobox should not be closed using arrow keys |
Fixed | |
VIS-1576 | Improvement | KeyboardHandling: There should be events when the selection changes |
Fixed | [[GENERAL]] Use a function block, which implements ISelectionManagerListener. Add the listener to ISelectionManager2. Both interfaces are in library VisuElemBase. See comments there for further information. |
VIS-1495 | Improvement | Trend: X-axis date time range updating via IEC variable |
Duplicate | [[GENERAL]] This issue has been resolved with VIS-1011. |
VIS-1011 | Improvement | Visu, Trend: Determine trend start and end time as IEC variable |
Fixed | [[GENERAL]] There are now two new control variables for the trend: Date Range Start and Date Range End. These variables contain the current trend time range values. They can be used to control the trend by changing their values. The trend stops or starts according to the values. |